Features

The i-meter® MF3 is a 3-element meter, compared to the i-meter® MF6 which is two 3-element meter. The i-meter® MF6 provides 1 extra 3-element meter in the same enclosure. This allows for the monitoring of Volts, Amps, KiloWatts, Power Factor, Frequency and Harmonics [V, I, kW, kVA, PF, Hz, THD (V/I)], of 2 meters in 1.

  • Innovative multifunction metering solution
  • Monitor multiple electrical Loads from the same distribution panel
  • Earn valuable LEED points
  • Track your energy consumption
  • Displays shows energy consumption; kilo-watt hours, volts, amps per phase, power factor and frequency
  • Flexible format to show rates, prices, date and time
  • Communicate with other equipment using radio signals, MODBUS or Bacnet communications protocols
  • Periodic collection and storage up to 45 days at 5-minute intervals
  • Applications: Residential, Commercial, Industrial

Cost-effective electric meter - Guide energy efficiency audits - Track your energy consumption

Interested? BUY NOW



Product Summary

i-meter® MF3 i-meter® MF6
Dimensions Inches 9.8H x 7.3W x 3.5D 9.8H x 7.3W x 3.5D
Dimensions Centimeters 275H x 185W x 89D 275H x 185W x 89D
Mounting Option Surface Mount Surface Mount
# of Meters 1 1 to 2
Meter Elements (CTs) 1 to 3 1 to 7 ( with Neutral)
Voltage Auto Ranging, 90 to 600 Volts (347V L-N) Auto Ranging, 90 to 600 Volts (347V L-N)
Service Type 1Ø2W, 1Ø3W, 2Ø3W, 3Ø4W wye, 3Ø3W Delta* 1Ø2W, 1Ø3W, 2Ø3W, 3Ø4W wye, 3Ø3W Delta*
Current Transformers 80/100 mA output, Self-Shorting 80/100 mA output, Self-Shorting
Instrument Transformer Interface Yes Yes
Memory 45 days (5 min intervals) kWh with PT2K 45 days (5 min intervals) kWh with PT2K
Pulse Output Wh/VAh Wh/VAh
Communications Modbus RTU, Bacnet MS/TP, RF, Ethernet, TCP/IP Modbus RTU, Bacnet MS/TP, RF, Ethernet, TCP/IP
Frequency 45 to 65 Hz 45 to 65 Hz
Accuracy Class 0.5 (Meets ANSI C12.20) 0.5 (Meets ANSI C12.20)
Real Time Measurements V, I, kW, kVA, PF, Hz, THD (V/I) V, I, kW, kVA, PF, Hz, THD (V/I)
Operating Temperature -10°C to +53°C -10°C to +53°C
Regulatory Compliance / Approvals Measurement Canada, CCSAUS, CULUS, CTEP (CA) Measurement Canada, CCSAUS, CULUS, CTEP (CA)
Patent U.S. Patent No. 8,049,487 U.S. Patent No. 8,049,487
*Delta systems require potential transformers

Downloads and Resources

Product Information Typical Drawings

Product Sheet

User Manual

i-meter® MF3 i-meter® MF6
Typical MF3 Metering Drawing Typical MF6 Metering Drawing
Typical MF3 c-w PTs Model Typical MF6 c-w PTs Model
120V 1ø2wire 120V 1ø2wire
120-240V 1ø3wire 120-240V 1ø3wire
120-208V 2ø3wire 120-208V 2ø3wire
120-208V 3ø4wire 120-208V 3ø4wire
240-416V 3ø4wire 240-416V 3ø4wire
347-600V 3ø4wire 347-600V 3ø4wire
600V 3ø3wire (Delta) 600V 3ø3wire (Delta)

Modbus Wiring Diagram